1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
September 25, 2025
Number of critical violations
1
Number of non-critical violations
4
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
311
Critical Interruption of Treatment
There is currently a boil water notice due to UV failure.
Corrective Actions: The UV system must be repaired. This repair must not be completed until a construction permit or waiver is obtained from our office. Timeline: Timeline for repair has not yet been set.
316
Non-Critical Source unprotected and subject to contamination
The wellhead does not have a proper cap/cover. It is covered by a tarp, plywood, and weighted top.
Corrective Actions: Repair the wellhead to provide a secure, vermin proof, watertight cap or cover. Timeline: Complete this repair within 3 month's time
317
Non-Critical Inadequate or improper construction of water works
Construction has occurred on the water system without approval from our office.
Corrective Actions: Provide the documentation required for a construction permit waiver or permit request for our office's review. This is for any waterline replacement or other construction that has occurred without approval. Timeline: Complete within 3 month's time
322
Non-Critical Emergency Response Plan
An emergency response plan has been submitted in 2012, but this information is outdated. A drought plan has also been submitted.
Corrective Actions: Update the ERP and review it annually. Timeline: Complete within 3 month's time
323
Non-Critical Other
An annual report has not been provided to water users or our office since 2018.
Corrective Actions: Complete the 2024 annual report and submit it to our office and provide it to the water users. Ensure all annual reports are completed within six months of the year's end. Timeline: Complete within 3 month's time