1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
November 5, 2024
Number of critical violations
1
Number of non-critical violations
4
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
313
Critical Operations and Maintenance /Other (specify below)
-Well needs to be repaired / upgraded to meet Ground Water Protection Regulation.
Corrective Actions: Hire Well Driller and address by June 2025 including flooding next to Well, adequate surface seal, soil sloping away from the Well, maintaining Well Cap.
314
Non-Critical Improper maintenance of distribution system
-Address Cross-connection between fire protection tank and water system. recommend block and bleed design.
316
Non-Critical Source unprotected and subject to contamination
-Put in place barriers to protect Well from vehicle damage.
Corrective Actions: Address by June 2025.
318
Non-Critical Inadequate Microbiological Analysis data
-Required to maintain semi-monthly bacteriological water sampling.
Corrective Actions: -Address immediately. (last sample received May 2024
322
Non-Critical Emergency Response Plan
-Provide current Emergency Response Plan by June 2025.