1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
October 1, 2025
Number of critical violations
0
Number of non-critical violations
2
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
318
Non-Critical Inadequate Microbiological Analysis data
Bacteriological samples are not being submitted as per required frequency.
Corrective Actions: Submit twice a month for your 3 sampling sites (Pumphouse Raw, Cafe Treat, Winery Tasting Room Treated).
320
Non-Critical Interruption of Treatment
UV Unit#2 (Viqua Pro 20 NSF55A) in alarm, red light flashing. Operator believes issue with flow sensor and recently installed larger pipe. Light intermittently turned red, and went back to green during inspection. Was green at the end of inspection. Operator stated they did not observe this until inspection.