Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
June 11, 2024
Number of critical violations
1
Number of non-critical violations
3
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
312
Critical Inadequate Treatment
The well has been identified as groundwater at risk of containing pathogens (GARP).
Corrective Actions: Therefore you are to complete the following: a) Sample the raw water well for total coliform and E.coli monthly over the next 24 months. This does not put a financial burden on the system as this testing is free and you are bringing in treated water samples anyways. This additional raw water sampling will further characterize the bacteriological quality of the well water. b) Have a professional complete a stage 2/3 analysis of the ground water as per BC provincial policy for wells at risk of containing pathogens. Have your professional engineer or professional geoscientist forward on their completed report onto this office.
317
Non-Critical Inadequate or improper construction of water works
UV by pass installed in HOPE LEARNING CENTRE pump/mechanical room.
Corrective Actions: Remove UV by pass. Next the well pump is pulled, increase well stick up to 30cm/12 inches above ground.
319
Non-Critical Inadequate Chemical Analysis Data
Full parameter chemical analysis is overdue.
Corrective Actions: Full parameter chemical analysis on the raw water. Supply by July 15, 2024 and forward results onto our office.
323
Non-Critical Other
Annual report for 2023 not completed.
Corrective Actions: Complete annual drinking water/report and forward onto your users and our office by June 30, 2024. THIS WAS COMPLETED JUNE 19, 2024.