1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
July 12, 2023
Number of critical violations
1
Number of non-critical violations
1
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
312
Critical Inadequate Treatment
System classified as Groundwater at Risk of containing Pathogens (GARP). Current treatment not adequate.
Corrective Actions: Implementation plan needs to be developed to address treatment upgrades. Discussed phased installation of cartridge filtration and in-line water meter prior to the install of a new UV unit. Provide Environmental Health Officer with a plan by October 30, 2023.
322
Non-Critical Emergency Response Plan
Emergency Response Plan contacts outdated.
Corrective Actions: Update plan to also include drought response. Templates provided to the Operator. Submit to Environmental Health Officer by August 31, 2023.