1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
September 16, 2026
Number of critical violations
0
Number of non-critical violations
2
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
314
Non-Critical Improper maintenance of distribution system
Free chlorine residual in the system has not been measured and recorded. No log available at the time of the inspection. Minimum required testing are one test from water leaving the retention tank and one test at the furthest point from the retention tank.
Corrective Actions: Obtain approved means of testing the chlorine residual in potable water for domestic use. Date to be corrected by: October 30th 2026
320
Non-Critical Interruption of Treatment
No chlorine residue detected in distribution line.
Corrective Actions: Chlorine residue must be present in the cistern and distribution. 0.2 ppm free available chlorine is to be present at the furthest point of the system to the pump room. Ensure to test water for Free Available Chlorine.