1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
15 - 300 Connections
Inspection Type
Routine
Inspection Date
June 19, 2025
Number of critical violations
1
Number of non-critical violations
1
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
312
Critical Inadequate Treatment
Untreated surface water is being supplied to all connections. The current and historical bacteriological tests indicate there are pathogenic organisms in the source. There are significant challenges with implementing different forms of treatment and upgrades to the system, as mentioned above (power, space restraints and consistent pressure). Residents and land owners have sincere concerns of treatment technologies that may compromise forest ecology.
Corrective Actions: All water suppliers must provide potable water to all users they supply. Surface water sources must as a minimum, receive disinfection (DWPR, S. 5) to reduce the risks from viruses, protozoa and other potential pathogens that may contaminate drinking water. Treatment must meet objectives stated in "Drinking Water Treatment Objectives (Microbiological) for Surface Water Supplies in B.C." using a multi-barrier approach: • 4-log reduction or inactivation of viruses. • 3-log reduction or inactivation of Giardia and Cryptosporidium. • Two treatment processes for surface water. • No detectable E. Coli, fecal coliform and total coliform An updated assessment to suggest treatment methods that work around challenges is required if the Water Supplier intends to continue supplying drinking water to users. Included in this could be a survey of current uses of the water supply at each point of the distribution system - for example, whether the water is used for domestic drinking water or for irrigation and washing down equipment/boats only, whether users have an alternative source or Point of Use/Entry system that is routinely and privately maintained. The Permit Terms and Conditions could be reviewed after the assessment and survey.
319
Non-Critical Inadequate Chemical Analysis Data
Chemical water sample has not been submitted since April 2016. This is due every 5 years as a condition of the Operating Permit.
Corrective Actions: Please ensure to submit a full spectrum chemical and physical analysis as soon as possible. Details will be sent to the operator by email.