This facility was given a Low hazard rating. More info


Inspection Information

Facility Type

15 - 300 Connections

Inspection Type

Routine

Inspection Date

July 21, 2026

Number of critical violations

0

Number of non-critical violations

1



Violations:
A summary of the violations found during the inspection are listed below.


Code
Description

314

Non-Critical Improper maintenance of distribution system

Chlorine residual measured 0 ppm in the distribution system. The operator stated much of the water system was not in use, which may have lead to stagnant water in the lines.

Corrective Actions: Ensure chlorine residuals are maintained between 0.2-0 ppm and tested regularly. Dead end lines and the distribution system should be flushed routinely to remove stagnant water.



Comments
Comments: Source: A single deep well is the sole primary source. The well head was in good condition and the well tag was affixed to the well head. (Well ID Plate #25421). Treatment: Cartridge filtration contains 5 micron and 1 micron ( absolute) filters. Two sets of filters are located in parallel. Chlorine is dosed after the filters and before the cistern, A tap is located after the cistern to sample for chlorine disinfection. Chlorine is to be measured after the cistern and at the furthest point in the distribution. Storage: Consists of a single 3000 US gallon tank. A water level meter was being installed at the time of the inspection. The cistern was secure and in good condition. Distribution system: Housing project is still moving in new residents. It is recommended to regularly flush the lines to remove stagnant water. Chlorine residuals must be maintained between 0.2-2 ppm in the furthest point in the distribution system. It is recommended each connection in the distribution system have a water meter for easier leak detection. Emergency response plan and documentation: The ERP is to be reviewed and updated annually or as needed. Operator to ensure annual reports are completed for each year and a copy made available by June 30th of the following year. Maintenance records must be kept on site and provided up request. Water sampling: Bacteriological samples are to be collected bi-weekly. Chemical analyses are to be provided to the DWO every 5 years or as requested.