Island Health
1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
2011 Franklin River Road Port Alberni, BC V9Y 1V2
This facility was given a Low hazard rating. More info


Inspection Information

Facility Type

15 - 300 Connections

Inspection Type

Routine

Inspection Date

October 26, 2026

Number of critical violations

0

Number of non-critical violations

5



Violations:
A summary of the violations found during the inspection are listed below.


Code
Description

314

Non-Critical Improper maintenance of distribution system

No operator on-site with small water systems training. The water supplier must designate a water operator who has training in water system operations.

Corrective Actions: Identify this person and complete the smaller water systems training (e.g., BCWWA's Small Water System course).

316

Non-Critical Source unprotected and subject to contamination

Well house door has light shining through the crevices in closed position. This can allow for potential pest entry to the source water housing.

Corrective Actions: Implement door sweeps or tighter seals. After these repairs are completed, clean the pumphouse to allow for monitoring of effectiveness of repairs. Ensure all other possible entry points are screened and sealed in a manner that prevents ease of access for pests/rodents. Deadline: 2 weeks.

318

Non-Critical Inadequate Microbiological Analysis data

Finished water samples have shown periodic positive total coliform results, while the submitted raw water results have not indicated the presence of total coliforms. This may suggest potential contamination within the reservoir or distribution system.

Corrective Actions: Propose a distribution system sampling plan that includes locations near the reservoir and at representative points throughout the distribution system. The sampling plan should assist in identifying potential areas of compromised system integrity, biofilm accumulation, or inadequate flushing and disinfection (shocking) that may contribute to the periodic positive total coliform results. Submit the proposed sampling locations and schedule for review. Deadline: 2 weeks.

322

Non-Critical Emergency Response Plan

An emergency response plan has been submitted in June 15, 2021, but this information is outdated. The drought component was submitted: May 1, 2023.

Corrective Actions: Take the following actions: 1. Draft and submit an Emergency Response Plan to the area EHO. Templates will be emailed to the operator. Review the provincial ERP guideline to ensure all required components are addressed. 2. Update the ERP and review it annually.

323

Non-Critical Other

The annual report for 2025 was not submitted before June 30.

Corrective Actions: Take the following actions: 1. Complete the 2025 annual report and submit it to our office. 2. Provide a copy to all water users. 3. Ensure all annual reports, moving forward, are completed within six months of the year's end (June 30).



Comments
The water source is a single deep well with a new well ID plate #78152 (previously #13895 - unregistered). It is unclear if we have the correct well log at this time as there were two other wells on the property. One no longer exists and one is located in the pumphouse (adjacent to the existing). The well water is pumped into a steel reservoir which serves a campground with amenities and an office. There was previously a concrete reservoir, and it is unclear when it was taken out of use. The Groundwater at Risk of Containing Pathogens (GARP) assessment is underway. The chemical analysis was last submitted November 2024; all parameters were found to be in accordance with GCDWQ. CONNECTIONS: 164 POPULATION: 400 WATER SYSTEM: 1. Deep Well #78152 (in wellhouse). 2. Two filters in parallel (exact type is unknown at this time). 3. Steel reservoir 16,000 imp gal. EOCP STATUS: Small water system. Action items: 1. BACTERIOLOGICAL TESTING (RAW WATER): Raw water sampling has not been conducted regularly, with the most recent submitted sample dated September 14, 2026. ACTION: Continue biweekly raw water sampling for at least one year to establish a sufficient dataset to assess potential source water contamination and determine whether the well is under the direct influence of surface water (GARP). 2. ASSESSMENTS: Island Health has developed a Source and System Assessment. Small water systems will be required to complete this assessment to address vulnerabiltiies related to their system. ACTION: Complete the provided Source and System Assessment (SASA) by: December 1, 2026. 3. OTHER: - Acquire the specifications for the two water filters used in the pumphouse. - Locate the existing operation and maintenance manuals for all components of the water system. If there's none, create one and send the draft version to area EHO. Resources are to follow in email. - Locate documentation confirming when the steel reservoir was last cleaned and when the concrete reservoir was decommissioned. - Verify whether the existing well log attached to the water licence corresponds to Well ID: 78152. - Maintain physical records of pumphouse cleanouts, such as a sanitation schedule, and retain copies of invoices and maintenance records from the plumbing company detailing the specific work completed. Consult the Health Authority before making alterations to major components of the water system, as a construction permit or waiver may be required. - Update the Area EHO on interventions completed to prevent unauthorized public access to the reservoir, as a ladder provides access and the reservoir lid is not secured with a lock. - Provide the Area EHO with an update on plans to retain a water technician to assess the overall water system, including the condition and integrity of the concrete reservoir and distribution system, to identify potential points of contamination. Comments: - The operator noted that maintenance of the two water filters in the pumphouse is conducted by a third-party plumbing company. - The pumphouse cleanout is reportedly conducted three to four times per year. - Routine leak detection is reportedly conducted daily, except during the winter. - Additional screening has been installed at the bottom of the steel reservoir vent pipe. Further reinforcement may still be required. - The reservoir was not observed to be leaking during this visit. - Repair work was conducted around the well cap, and the previously existing hole was no longer visible during this visit.