Island Health
1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
790 North Road Gabriola Island, BC V0R 1X2
This facility was given a Low hazard rating. More info


Inspection Information

Facility Type

2-14 Connections

Inspection Type

Routine

Inspection Date

October 8, 2026

Number of critical violations

0

Number of non-critical violations

2



Violations:
A summary of the violations found during the inspection are listed below.


Code
Description

323

Non-Critical Other

Annual Report for 2025 not submitted/completed.

Corrective Actions: Operator to complete 2025 Annual Report and all subsequent Annual reports by April 30th of each year (i.e. 2026 Report due April 30/27).

323

Non-Critical Other

Water system does not have Operator with Water Safe or equivalent.

Corrective Actions: Water Operator staff member to complete Thomson Rivers University Water Safe or equivalent by December 31 2026.



Comments
1 - Full parameter chemical analysis was completed July 23/24 pH was low, sodium/turbidity and total organic carbon were all elevated. If operator is to chlorinate water supply, ensure disinfection by-product POTENTIAL testing is completed prior containing a professional or applying for a Construction Permit for proposed equipment installation, 2 - Regarding water system maintenance: • Daily checks of water system are completed by staff and written in log book. • Cartridge filters are changed every 3 months and are in the following sequence 50 -> 5 micron, carbon, 25 -> 1 Micron. Quartz tubes are cleaned every 3 months (operator to use CLR as per manufacturers directions -> see attached). Sensors have been replaced several times. • UV is in alarm and will go into alarm soon after cartridge change or UV quartz tube cleaning, all times of the year. UV solenoid will shot of water to system when alarm is strong/fully engaged. • cistern/reservoir heat deflectors removed in fall and will re-reinstalled prior to elevated temperatures in May/June 2027. • Cistern cleaning company attended site in 2025 and water hauling company complete visual check of reservoir when filling occurs. 3 - Drought information: • 4 Loads of water have been purchased due to low well productivity and drought. A fifth load was purchased but this was due to staff error with water tap. 4 - Water sampling frequency met requirements listed in Operating Permit. There were a couple of total coliform results in (20258/2026 but resamples were always satisfactory (met requirements). 5 - Raw water bacteriological for the last 2 years has shown consistent total coliforms in raw water samples (see attached sample results). Operator to follow Groundwater at Risk of Containing Pathogens (GARP) and treat as per BC Ministry of Health groundwater supplies (microbiological) or conduct level/stage 2 and 3 investigation and risk management as per GARP determination as per BC Ministry of Health Guidance sent in 2024.