Island Health
1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
730 Quathiaski Cove Road Quathiaski Cove, BC V0P 1N0
This facility was given a Moderate hazard rating. More info


Inspection Information

Facility Type

1 Connection

Inspection Type

Routine

Inspection Date

July 29, 2026

Number of critical violations

2

Number of non-critical violations

7



Violations:
A summary of the violations found during the inspection are listed below.


Code
Description

312

Critical Inadequate Treatment

- GARP Assessment of Well "Ground Water At Risk Of Containing Pathogens" has been re-assessed. A copy of the report is provided with this inspection report and how assesses the Well as "At Risk - GARP". The At Risk Assessments relates to intermittent total coliform counts and elevated turbidity in Well, the aquifer being fractured crystalline bedrock and community sewer main within 50 feet of Wellhead.

Corrective Actions: - By March 2027 apply to our office for a Construction Permit or Waiver to upgrade the water system treatment to comply with Drinking Water Treatment Objectives (microbiological) for Ground Water Supplies in BC. The Treatment System will also need to effectively and reliably trat source water quality for maintaining effective disinfection. For the function of UV devices this would include turbidity, color, iron, manganese and tannins, all of which have been repeated issues from the source and after treatment and impact effective ultra violet transmittance.

313

Critical Operations and Maintenance /Other (specify below)

- Construction / Alteration / Upgrades of water system without Construction Permit or Waiver. Recent additions of Katalox Iron + Manganese Filter without Construction Waiver from Public Health Engineer, history of treatments changes without Construction Waiver in some incidents.

Corrective Actions: - All upgrades, alterations or extensions to water system requires Construction Permit or Waiver from Public Health Engineer prior to construction.

317

Non-Critical Inadequate or improper construction of water works

- Regarding MIFAB min - 500 npb devices connected to floor drain p-traps, provide update to our office on how back-flow prevention is addressed that complies with CSA Standard CAN/CSA B64.

Corrective Actions: - Provide update October 2026.

318

Non-Critical Inadequate Microbiological Analysis data

- Routine bacteriological testing is being changed to semi-monthly at Well and two Distribution sample sites.

Corrective Actions: - Ensure updated sampling frequency is maintained and lab reports are forwarded to our office for review as soon as possible.

319

Non-Critical Inadequate Chemical Analysis Data

- April 15 2025 testing at the Janitor Sink for Lead came back with 9.8ug/L. Additional testing and follow-up is needed to try and verify the cause of the results, if it is an ongoing issue for the water supply, and if needed how to resolve if counts are continuing above 5ug/L.

Corrective Actions: - Perform Lead Testing at the Source, Janitor Sink, Staff Sink and Public Washroom sink on the same day. Test after the water sits over night before any flushing, and all sample sites again after they were flushed for 3 - 5 minutes, Provide update October 2026.

319

Non-Critical Inadequate Chemical Analysis Data

- Updated performance testing is being required for UVT, turbidity, color, Iron, tannins and Manganese. Ensure all are sampled from the source and just before the UV Device on the same day.

Corrective Actions: - Provide performance testing in October 2026 and again by March 2027 to review performance of source and treatment.

323

Non-Critical Other

- Cut back brush near Wellhead, maintained ideally ~20+feet away.

323

Non-Critical Other

Develop and maintain a written Maintenance Plan for the water systema nd a Protection Plan for ~ 100 Feet around the Wellhead.

Corrective Actions: - Provide copies of plans by March 2027, include, maintenance schedule for all filter media and UV device operation, around the Well, identify potential risks and how they will be prevented or mitigated, and Monitoring Plan

323

Non-Critical Other

- Updated Emergency Response Plan for the following; - Corrective actions for UV device, Chlorine no longer in place. - Note all potential threats to providing potable water are notified to Drinking Water Officer as soon as reasonably possible. - Posting or rescinding water quality notices should be done in consultation with Drinking Water Officer - No By-passing UV Device automatic shut-off device without consulting with Drinking Water Officer and likely going on water quality notice.



Comments
Routine Inspection: Currently only serving bathrooms and staff sink, Take-out not connected, ship no longer filled. Notes: Prior to inspection application received to install upgraded Treatment System, including, Katalox Iron + Manganese Filter, Reverse Osmosis and Neutralizing Filter. - Treatment system in place at time of inspection - Next Sand Filter, 50/5 Micron Filter, Tannin Filter, Iron + Manganese Filter(new)(Katalox), Cat Carbon Filter, I Micron Absolute Filter, Viqua Pro 10 UV Device, 8800 Litre Storage. - Chlorine Disinfection in file history no longer connected (CP Waiver in 2023) Note: A potential alternative to upgrading the Treatment System as directed in the report is to pursue application and approval to become a permitted non-potable water supply system. - If remaining a potable water system after upgrades are completed the fixed Take-Out Food Facility should be connected to the potable water system. - Notice of Proposed Permit Conditions updates provided.