Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
May 2, 2024
Number of critical violations
2
Number of non-critical violations
2
311
Critical Interruption of Treatment
The visual alarm was on the UV.
Corrective Actions: CORRECTED - the UV was repaired.
312
Critical Inadequate Treatment
The water system does not meet the Drinking Water Treatment Objectives (Microbiological) for Surface Water Supplies in British Columbia.
Corrective Actions: Take the following actions: 1. Complete the chemical analysis to allow for a source approval to be completed. 2. Determine an action plan and timeline for completing any required works to meet these objectives. 3. Complete the objectives as per agreed upon timeline Note: the correct by date is set for the implementation plan.
318
Non-Critical Inadequate Microbiological Analysis data
Bacteriological analysis has not been completed at agreed upon frequency.
Corrective Actions: Take the following actions: 1. Complete bacteriological analysis at the agreed upon frequency of 2 samples biweekly. 2. Complete raw water sampling quarterly. CORRECTED - sampling has commenced
319
Non-Critical Inadequate Chemical Analysis Data
Chemical analysis has not bee completed for the system.
Corrective Actions: Complete chemical analysis for raw surface water parameters provided and submit the results to our office.