Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
April 30, 2024
Number of critical violations
2
Number of non-critical violations
4
311
Critical Interruption of Treatment
The UV was alarming and not properly functioning.
Corrective Actions: Take the following actions: 1. Issue a boil water notice. 2. Follow the requirements to remove the boil water notice (repair the UV and obtain two consecutive satisfactory bacteriological samples 24 hours apart).
312
Critical Inadequate Treatment
The water system does not meet the Drinking Water Treatment Objectives (Microbiological) for Surface Water Supplies in British Columbia.
Corrective Actions: Tale the following actions: 1. Determine an action plan and timeline for completing any required works to meet these objectives. 2. Complete the objectives as per agreed upon timeline.
317
Non-Critical Inadequate or improper construction of water works
Additional disinfection devices have been installed without a construction permit or waiver (UV).
Corrective Actions: Submit all the required documentation as outlined in the Construction Permit Waiver Request Form for review.
318
Non-Critical Inadequate Microbiological Analysis data
Bacteriological sampling has not been submitted to meet the minimum requirements of the Drinking Water Protection Schedule B.
Corrective Actions: The sampling schedule has been updated. Ensure to meet the approved sampling schedule 2 samples biweekly.
319
Non-Critical Inadequate Chemical Analysis Data
A chemical analysis was completed in 2002. This should be completed every 3-5 years (next due ASAP). No additional or parameter specific testing is required at this time.
Corrective Actions: Complete a full chemical analysis and submit the results to our office.
322
Non-Critical Emergency Response Plan
The full emergency response plan (ERP) has not been submitted to our office.
Corrective Actions: Submit the ERP to our office.