Facility Type
1 Connection
Inspection Type
Routine
Inspection Date
May 10, 2024
Number of critical violations
0
Number of non-critical violations
3
319
Non-Critical Inadequate Chemical Analysis Data
The chemical sample results dated April 1, 2020 report a manganese concentration of 0.035 mg/L.
Corrective Actions: Please resample this parameter to confirm the concentration, given the recommended concentration of manganese entering the distribution system is 0.015 mg/L. Alternatively, please consider the option of conducting a full-spectrum chemical analysis which is due every five years and will be required for this water system in 2025. The list of parameters is enclosed.
322
Non-Critical Emergency Response Plan
Corrective Actions: An Emergency Response Plan (ERP) is required to be in place for all water supply systems. This office has received the drought-specific ERP for this water system. Please also submit a general ERP to this office no later than May 31, 2024. An ERP template has been enclosed.
323
Non-Critical Other
Corrective Actions: Please confirm with the water treatment designed that the washroom hand washing basins also receive only non-treated water.