Public Swimming Pool/Spa Inspection Report | Follow-Up
June 11, 2024
Demerits & Grade:
Grade:
Observations & Corrective Actions
30: Observed unable to demonstrate SVRD system Corrective Actions: Ensure a SVRD system is in proper working condition
33: Observed no spare main drain cover and no date of install Corrective Actions: Ensure spare is available at all times and replaced according to date of install
34: Observed multiple drains within 3ft of each other Corrective Actions: Ensure SVRS is working properly when drains are within 3ft of each other
37: Observed no vacuum gauge provided for suction site of pump
39: Observed no labels on piping for flow and direction
47: Observed no weirs provided on skimmers
51: Observed light in spa not functioning Corrective Actions: Bottom of the pool and drains must be illuminated at all times
53: Observed pumps not grounded
56: Observed direct connection of pipes and back wash dispelling directly onto ground
112: Observed areas of fence less than 48inches
113: Observed all 3 gates not closed properly and latching, all repaired on site at time of inspection.
114: Observed glass door leading into the pool enclosure proped open
121: Observed a concrete change in elevation next to rear gate, fence and enclosure creating climbable structure.
129:
Additional Comments
Spa closed due to lack of properly working underwater light and unable to demonstrate SVRD is working Establishment must comply with the state newly adopted signage requirements. Correct all findings prior to contacting inspector for reinspection and to obtain written authorization.
Observations
Swimming Pool
NA
1 Chlorine (1-8 ppm) Bromine (2.5-12ppm)
Compliant
Observations
Spa
NA
18 Cholrine (2-8ppm) Bromine (4.5 - 12ppm)
Compliant
Observations
NA
19 pH (7.0 - 7.8)
Compliant
Observations
NA
20 Cyanuric acid (100 ppm or less)
Compliant
Observations
IN
22 Emergency shutoff in sight & minimum 5 ft. away.
Compliant
Observations
Suction Outlets (Main Drains)
OUT
30 Single suction outlet - SVRD or AVS installed/maintained.
Observed
Observations
OUT
33 Suction outlet VGBA / ASME/ANSI compliant & extra main drain cover.
Observed
Observations
OUT
34 Single or Dual main drain(s) and minimum 3 feet apart.